4-71
Group 01 V/F Control Parameters
01- 00 Volts/Hz Patterns
Range 【0~FF】
Make sure to set the inverter input voltage parameter 01-14
There are three ways to set V/F curve:
(1) 01-00 = 0 to E:Choose any of the 15 predefined curves (0 to E)
(2) 01-00 =0F:Use 01-02~01-09 and 01-12~01-13, with voltage limit
(3) 01-00 = FF:Use 01-02~01-09 and 01-12~01-13, without voltage limit.
Refer to the following figure:
The default parameters (01-02~01-09) are the same when 01-00 is set to F (default) and 01-00
is set to 1.
Parameters 01-02 to 01-13 are automatically set when any of the predefined V/F curves are
selected. Please refer table 4.3.3~4.3.5 for the features of V/F pattern.。
When V/F curves are selected, frequency will be limited by 00-12 and 00-13.
This parameter is not affected by the initialization parameter (13-08)