4-100
Group 02 IM Motor Parameters
02- 00 No-load current of motor 1
Range 【0.01~600.00】A
02- 01 Rated current of motor 1
Range
Lower limit: 10% rated current of V/F mode, 25% rated current of SLV mode
Upper limit: According to inverter’s rated current
02-03 Rated rotation speed of motor1
Range 【0~60000】rpm
02- 04 Rated voltage of motor1
Range
200V:【50.0~240.0】V
400V:【100.0~480.0】V
02- 05 Rated voltage of motor1
Range 【0.01~600.00】KW
02-06 Rated frequency of motor 1
Range 【4.8~599.0】Hz
02-07 Pole of motor 1
Range 【2~16】
02-09 Excitation current of motor 1 <1>
Range 【15~70】% motor rated current
02-10 Core saturation coefficient 1 of motor 1 <1>
Range 【1~100】%
02-11 Core saturation coefficient 2 of motor 1 <1>
Range 【1~100】%
02-12 Core saturation coefficient 3 of motor 1 <1>
Range 【80~300】%
02-13 Core loss of motor 1
Range 【0.0~15.0】%
02-19 No-Load Voltage of motor 1
Range
200V:【50~240】V
400V:【100~480】V
Motor parameters are automatically set when performing an auto-tune (17-10=1). In most
case no adjustment is required after performing an auto-tune except when using the
inverter in special applications (e.g. machine tool, positioning, etc…).
Please refer to parameter group 22 for permanent magnet motor parameters.
Motor no-load current (02-00).
Value is calculated based on the motor rated frequency (17-05) and motor rated current (17-03).