4-110
Figure 4.3.18 9-speed timing diagram
*1:When 00-05=1, multi-speed frequency reference is set by analog input AI1 or AI2.
When 00-05=0, multi-speed frequency reference is set by 05-01.
(8) Forward jog run command (03-0X=06)
(9) Reverse jog run command (03-0X=07)
Jog command has a higher priority than other frequency reference commands.
Jog command uses stop mode set in parameter 07-09 when Jog command is active > 500ms
(10) 03-0X =08:UP frequency command
(11) 03-0X =09:Down frequency command
Inverter can use digital operator and external digital input (S1~S6) to increase or decrease
output frequency while motor is running.
When inverter uses external digital input to perform UP/DOWN, set 00-02=4, 00-05=4
and 03-00~03-05=8 and 9, it requires both UP and DOWN functions 08 and 09 to be
programmed to the two digital input terminals.
UP/DOWN frequency command follows standard acceleration and deceleration times
“SE02” DI terminal error will be displayed when:
①. When only the UP or DOWN command function is programmed to the digital inputs.
②. When both DOWN command and Inhibit Acceleration/deceleration command are activated
simultaneously
③. When both UP command and Inhibit Acceleration/deceleration command are activated
simultaneously.