4-112
(12) Acceleration/deceleration 1 selection (03-0X=10)
Refer to the "multi-function digital input terminals select acceleration / deceleration time” .
(13) Inhibit Acceleration/deceleration command (03-0X=11)
Operation of inhibit Acceleration/deceleration function, please refer figure 4.3.21。
The frequency reference value is saved when the acceleration/deceleration inhibit command is
active, the frequency reference value is saved even when powering down the inverter.
Figure 4.3.21 Inhibit acceleration / deceleration command operation
(14) Main/ Alternative Run Switch Function (03-0X =12)
When function terminals conduct, run command source is set in alternative run command
(00-03). When functional terminal is set to 27 (Local/ Remote control selection), it will be
precedential to main/alternative run switch.
(15) Main/ Alternative Frequency Switch Function (03-0X =13)
When function terminals conduct, frequency command source is set in alternative frequency
command (00-06). When functional terminal is set to 27 (Local/ Remote control selection), it
will be precedential to main/alternative frequency switch. When PID function is
active(10-03=XXX1B), this function is invalid and main frequency is switched to PID function.
When PID function is invalid, Main/ Alternative frequency switch function is valid then.
(16) Emergency stop (decelerate to zero and stop) (03-0X =14)
Refer to the "deceleration time of emergency stop" of parameter 00-26
(17) External Baseblock Command (coast to stop) (03-0X =15)
Execute the base block command by the use of ON / OFF way of multi-function digital
input terminal, and prohibit the inverter output.