EasyManua.ls Logo

TECO E510s Series - Page 183

TECO E510s Series
425 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4-117
(40) PID Control Disable 2 (03-0X=66)
(41) External Fault (03-0X=68)
When this function is enabled, inverter will stop running and motor will coast to stop.
When digital input (S3) set to external fault, keypad will display EF3 Ext. Fault (S3)”.
All digital input terminals can be set to external fault.
(42) Externl Overload (03-0X=69)
When this function is enabled, inverter will stop running and motor will coast to stop.
When digital input (S5) set to external fault, keypad will display TOL Ext. OverLoad
Fire mode needs to be enabled first (08-48=1) when external overload function needs to be
used. Only S5 terminal can be set to external overload input.
External overload function will be set to normal close contact. Pleae do not set run command
from external source.
03- 06 UP/DOWN Frequency Step
Range 【0.00~5.00】Hz
When 03-06=0Hz, UP/DOWN function will be kept.
When 03-06≠0Hz, frequency command becomes operation frequency plus 03-06 value.
Example:
03- 00=8 (S1 terminal is increasing frequency command)
03- 01=9 (S2 terminal is decreasing frequency command)
03- 06=Hz
Mode 1:
When 03-06=0, UP/DOWN function will be kept.
Mode 2:
When 03-060 and the turned on period is less than 2 secs, for every ON operation frequency
changes by Hz.

Table of Contents

Other manuals for TECO E510s Series

Related product manuals