4-154
The speed search cannot be used when the motor rated power is greater than the inverter
rated power.
In V / F mode, it is necessary to perform a static auto-tune.
In SLV mode, it is necessary to perform a rotational auto-tune. Perform a static auto-tune when
using long motor leads.
Speed Direction Search Operating Current (07-19)
(1) Used in bidirectional speed search only (07-24 = 1).
(2) Set bidirectional current level.
(3) Increase value if speed search is not successful at low speeds (above 5Hz)
Note:
If value is too high may cause DC braking effect.
Speed Search Operating Current (07-20)
(1) Can be used for bidirectional (07-24 = 1) or unidirectional (07-24 = 0) speed search.
(2) Sets speed search current Level.
(3) The set value must be lower than the excitation current (02-09) and must equal to the no-load
current. If the no-load current is unknown it is recommended to set value at 20%.
(4) Excessive speed search current will cause inverter output to saturate.
(5) It is recommended to use speed search in case of a momentary power loss. Increase the
minimum base block time (07-18) in case of an over-current condition.
Integral time of speed searching (07-21)
(1) Can be used for bidirectional (07-24 = 1) or unidirectional (07-24 = 0) speed search.
(2) Set the integral time during speed search.
(3) If OV occurs, increase the set value to increase the speed search time. Decrease the value if a
quick start is required.
Delay time of speed searching (07-22)
(1) Use delay time (07-22) when using a contactor on the inverter output side.
(2) Speed search delay time is disabled when set to 0.0 sec. (07-22 = 0.0)
Voltage recovery time (07-23).
(1) Sets the voltage recovery time.
(2) Sets the time for the inverter to restore the output voltage from 0V to the specified V/f level
after speed search function is completed.
Direction-Detection Speed Search (07-24):
(1) 07-24=1, enable direction-detection speed search:
At start the current controller will send a step current to the motor (07-19) to determine the
motor direction. Once direction is determined the current controller will perform a speed
search using speed search operating current defined in parameter 07-20. Speed search is
executed after a momentary power loss (external speed search command 2, 03-00 to
03-05=34) or from max. frequency (external speed search command 1, 03-00 to 03-05=19).
Speed search direction will follow the speed command.