4-158
Group 08 Protection Parameters
08- 00 Stall prevention function
Range
【xxx0b】:Stall prevention function is enabled during acceleration.
【xxx1b】:Stall prevention function is disabled during acceleration.
【xx0xb】:Stall prevention function is enabled during deceleration.
【xx1xb】:Stall prevention function is disabled during deceleration.
【x0xxb】:Stall prevention function is enabled during operation.
【x1xxb】:Stall prevention function is disabled during run.
【0xxxb】:Stall prevention function during run is based on the first
acceleration time.
【1xxxb】:Stall prevention function during run is based on the second
acceleration time.
08- 01 Stall prevention level during acceleration
Range 【20~200】%
08- 02 Stall prevention level during deceleration
Range
200V :【330V~410V】
400V :【660V~820V】
08- 03 Stall prevention level during run
Range 【30~200】%
08-21 Limit of stall prevention during acceleration
Range 【1~100】%
08-22 Stall prevention detection time during run
Range 【2~100】mSec
08- 40 Motor 2 Acceleration Stall Prevention Level
Range 【20~200】%
08-41 Motor 2 Acceleration Stall Prevention Limit
Range 【1~100】%
Note:Stall prevention function only can be set in V/F control mode.
Stall prevention during acceleration (08-00=xxx0b)
(1) Prevents the inverter from faulting (Overcurrent, Motor overload, Inverter overload) when
accelerating with heavy loads.
(2) When the inverter output current reaches the level set in parameter 08-01 minus 15% the
acceleration rate starts to decrease. When the inverter output current reaches the level set in
parameter 08-01 the motor stops accelerating.
(3) Reduce stall prevention level during acceleration (08-01) in case the motor stalls (when the
motor power is smaller than the inverter rating.