4-164
08- 24 Operation Selection of External Fault
Range
【0】:Deceleration to Stop
【1】:Coast to Stop
【2】:Continous Operation
When multi-function digital input terminal is set to 25 (the external fault) and this terminal
signal is triggered off, parameter 08-24 (Operation Selection of External Fault) can be selected
to stop it. The selection of stop modes is the same as 07-09.
08- 25 Detection Selection of External Fault
Range
【0】:Immediately Detect when the Power is Supplied
【1】:Start to Detect During Operation
The reson for the detection of external faults is determined by parameter 08-25.
(1) When 08-25=0, faults are immediately detected at power up.
(2) When 08-25=1, fault are detected when the inverter is running.
08 - 35
Motor Overheat Fault Selection
Range
【0】:Disable
【1】:Coast to Stop
【2】:Free run to top
【3】:Keep running
08 - 36
PTC Input Filter Time Constant
Range
【0.00 ~ 5.00】
08 - 39
Delay Time of Motor Overheat Protection
Range
【1 ~ 300】Sec
08 - 42 PTC Protection Level
Range 【0.1 ~ 10.0】V
08 - 43 PTC Restart Level
Range 【0.1 ~ 10.0】V
08 - 44 PTC Warning Level
Range 【0.1 ~ 10.0】V
Motor Overheat Fault Selection:
It executes motor overheat protection by the resistor (PTC) that built-in the motor.
The resistor (PTC) is between AI2 and GND and a divided resistor R ,as the pic 4.3.65(b)
(1) When motor occurs overheating:
08-35 = 0:Motor overheats fault function is off.
08-35 = 1:When the motor is overheating, it coasts to stop.
08-35 = 2:When the motor is overheating, it free runs to stop
08-35 = 3:When the motor is overheating, it keeps running until reach the value of 08-42
(2) 08-35=1 or 2, if the temperature is getting higher for the motor and AI2 voltage level is
higher than the value of 08-44, the display will show 『OH4 Motor Overheating』 and the motor
will stop by 08-35=1 or 2.
(3) 08-35=3, When the temperature is getting higher for the motor and AI2 voltage level is higher
than the value of 08-44, the display will show 『OH3 Motor Temp Warning』but the motor
continues running. But AI2 voltage level is higher than the value of 08-42 and the time reach to
08-39, the motor free runs to stop.
(4) When 08-35 = 1 or 2 or 3,When the motor cools down and AI2 voltage level is lower the value
of 08-43, 『OH4 Motor overheat』will reset.