Figure 4.3.82 PID feedback loss detction
10-15 Integral Value Resets to Zero when Feedback Signal Equals the Target Value
Range
【0】:Disable
【1】:1 Sec
【30】:30 Sec (Range:0 ~ 30 Sec)
When 10-15=0, As PID feedback reaches the set point, the integrator will not be reset to 0.
When 10-15≠0, As PID feedback value reaches the set point, reset to the setting value of 10-15
and inverter stops. The inverter will run again when the feedback value differs from the set
point value.
10-16 Allowable Integration Error Margin (Unit) (1 Unit = 1/8192)
Range 【0 ~ 100】%
Restart the tolerance after the integrator reset to 0.
10-17 Start frequency of PID sleep
Range 【0.00~599.00】Hz
10-18 Delay time of PID sleep
Range 【0.0~255.5】Sec
10-19 Frequency of PID wakeup
Range 【0.00~599.00】Hz
10-20 Delay time of PID wakeup
Range 【0.0~255.5】Sec
10-29 PID sleep selection
Range
【0】:Disable
【1】:Enable
【2】:Set by DI
10-40
Selection of PID Sleep Compensation Frequency
Range
【0】:Disable
【1】:Enbale