4-182
10-30 Upper Limit of PID Target
Range 【0 ~ 100】%
10-31 Lower Limit of PID Target
Range 【0 ~ 100】%
Target value of PID will be limited to the range of upper & lower limit of PID target.
10- 33 Maximum Value of PID Feedback
Range 【1~10000】
10- 34 PID Decimal Width
Range 【0~4】
10- 35 PID Unit
Range 【0~23】
When 10-33 (the maximum value of PID feedback) is active, it will become 100% the
corresponding value of 10-02.
Parameter 10-34 (PID decimal width) is used for rounding up setting.
For example:set 10-34=1, it displays XXX.X ; set 10-34=2, it displays XX.XX.
Parameter 10-35 (PID unit) is selected depending on user’s needs.
Note:When user switches PID in LED keypad, 10-33 is required to be lower than 1000 and 10-34=1,
otherwise the keypad will show a “SE05” alarm (PID setting error).
10- 39 Output Frequency Setting of PID Disconnection
Range 【0.00~599.00】Hz
When PID feedback disconnection is in alarm, frequency command output depends on the
setting value of 10-39. If the warning is lifted, PID control is restored.
10- 47 Proportioanl Gain (P) of Fire Mode
Range 【0.00~10.00】
10- 48 Integral Time (I) of Fire Mode
Range 【0.0~100.0】Sec
10- 49 Differential Time (D) of Fire Mode
Range 【0.00~10.00】Sec
PID functions of ire mode, please refer to parameter group 08.