4-186
Manual energy saving gain (11-12)
(1) When manual energy savings is enabled, output voltage of inverter will be determined by
parameter 11-12, output voltage is percentage gain times the V/F voltage.
(2) Manual energy saving control uses the voltage recovery time (07-23) to change the output
voltage.
Manual energy saving frequency (11-18)
Setting parameter 11-18 manual energy savings frequency to 0.0 Hz disables the manual energy
savings frequency activation function. Refer to figure 4.3.88
Figure 4.3.88 Manual energy saving operation
11- 14
OV Prevention Level
Range
230V :【200~400】V
400V :【400~800】V
11- 17
Acceleration/Deceleration Gain
Range
0.1~10.0
Parameter setting:
(1) If OV alarm still happened when 11-40=3, please increase the value of 11-17 in 0.1 unit.
(2) If the setting value of 11-17 is not suitable, the ripple of speed and current will be higher.
(11-14 is the target voltage of over-voltage prevention mode 3, its the voltage inhibition level.)
11- 28 Frequency Gain of Over Voltage Prevention 2
Range 1~200】%
11- 33 DC Voltage Filter Rise Amount
Range 0.1~10.0】V
11- 34 DC Voltage Filter Fall Amount
Range 0.1~10.0】V
11- 35 DC Voltage Filter Deadband Level
Range 0.0~99.0】V
11- 36 Frequency gain of OV Prevention
Range 0.000~1.000
11- 37 Frequency limit of OV Prevention
Range 0.00~599.00】Hz