4-194
12- 05 Status display of digital input terminal (LED / LCD)
Range Read-only
Terminal S1~S6 are represented using two segments of each digit. Segment turns on when
input is active.
Example 1:
S1/S3/S5/S6 are ON, S2/S4 are OFF, 12-05 will turn on when RY1 without output. (LED)
S1 S2 S3 S4 S5 S6
Example 2:
S2/S3/S4 are ON, S1/S5/S6 are OFF, 12-05 will turn on when RY1/RY2/DO1 output at the same time.
RY1
RY2
DO1
PLC
Please refer section 4.2 for instruction of parameter 12-11~12-43.
Please refer parameter setting of 12-38/12-39 for PID feedback and 10-33~10-35 for display.
Example 3:S1~S6, RY1 and RY2 are OFF