Group 12 Monitoring Parameters
12- 00 Display Screen Selection (LED)
Range
(Highest bit) 0 0 0 0 0 (Lowest bit)
The value range if each bit is 0~8 from the highest bit to the lowest bit
【0】:No display
【1】:Output current
【2】:No display
【3】:DC busvoltage
【4】:heatsink temperature
【5】:PID feedback
【6】:AI1 value
【7】:AI2 value
【8】:Counter
Notes:
The highest bit is used for power-up monitor. The 4 least significant bits can be used to customize
the display sequence see page 4-4.
12- 01 PID Feedback Display Mode (LED)
Range
【0】:Display the feedback value in integer (xxx)
【1】:Display the feedback value with one place after the decimal point (xx.x)
【2】:Display the feedback value (x.xx) with two places after the decimal point
12- 02 PID Feedback Display Unit Setting (LED)
Range
【0】:xxxxx (no unit)
【1】:xxxPb (pressure)
【2】:xxxFL (flow)
12- 03 Line Speed Display (LED)
Range
【0~60000】RPM
12- 04 Line Speed Display Mode (LED)
Range
【0】:Display Inverter Output Frequency
【1】:Line Speed Display at Integer. (xxxxx)
【2】:Line Speed Display at One Decimal Place. (xxxx.x)
【3】:Line Speed Display at Two Decimal Places. (xxx.xx)
【4】:Line Speed Display at Three Decimal Places. (xx.xxx)
When 12-04=0, Inverter displays the line speed at stop, operation or the modification of
frequency.
When 12-04≠0, 12-03 is set to the maximum line speed and corresponds to the maximum
output frequency.
For example:
If the line speed display of 12-03 is 1800, the keypad display is 900 when frequency output is 30Hz.