4-204
Group 16 LCD Function Group
16- 00 Main Screen Monitoring
Range
【5~43】
16- 01 Sub-Screen Monitoring 1
Range 【5~43】
16- 02 Sub-Screen Monitoring 2
Range 【5~43】
At power-up the inverter shows two monitor section on the display, main monitor section and
the sub-screen monitor section (smaller font).
Choose the monitor signal to be displayed as the main-screen monitor screen in parameter
16-00, and the monitor signals to be displayed on the sub-screen monitor in parameters 16-01
and 16-02, similar to monitor parameters 12-5~12-43.
16- 03 Display unit
Range
【0】:Frequency display unit is Hz (Resolution is 0.01Hz)
【1】:Frequency display unit is % (Resolution is 0.01%)
【2】:Frequency display unit is RPM
【3~39】:Reverse
【40~9999】:100% is XXXX with no decimals (integer only)
【10001~19999】:100% is XXX.X with 1 decimal
【20001~29999】:100% is XX.XX with 2 decimals
【30001~39999】:100% is X.XXX with 3 decimals
16- 04 Engineering Unit
Range
【0】: No Unit
【1】: FPM
【2】: CFM
【3】: PSI
【4】: GPH
【5】: GPM
【6】: IN
【7】: FT
【8】: /s
【9】: /m
【10】: /h
【11】: °F
【12】: inW
【13】: HP
【14】: m/s
【15】: MPM
【16】: CMM
【17】: W
【18】: kW
【19】: m
【20】: °C
【21】: RPM
【22】: Bar
【23】: Pa
Display unit of digital operator(16-03)
Set the units of the following items to be displayed, the frequency reference (05-01, 00-18,
06-01~06-15) and the monitoring frequency 12-16, 12-17 (Output frequency).
Display unit of engineering (16-04)
When 16-03 = 00040-39999, engineering units are enabled. The displayed set range and the
frequency range of unit (05-01, 06-01~06-15) as well as the monitoring frequency (12-16, 12-17)
are changed by parameters 16-04 and 16-03.