4-205
16-03 Set / displayed contents
0 0.01 Hz
1 0.01 % (maximum output frequency 01-02=100%)
2 Frequency display unit is RPM
3- 39 Reserved
00040 - 39999
Set the decimal point by using the fifth place
i.e. □ □□□□
Sets full display scaling excluding decimals
Set the number of decimal places
00040 - 09999: □□□□ (Integer only e.g. 1000 )
10001 - 19999: □□□. □ (1 decimal place e.g. 10.0)
20001 - 29999: □□. □□ (2 decimal places, e.g. 10.00)
30001 - 39999: □. □□□ (3 decimal places, e.g. 10.000)
<Example>:
16-03 Display
Display
Unit
Display example
00040-09999 □□□□
Use
16-04
Setting
100 % speed is 0200
Set 16-03=00200 (from 05-01, 06-01 to
06-15, set range from 0040 to 9999).
Set 16-04=0 (no unit)
10001–19999 □□□. □
100 % speed is 200.0 CFM
Set 16-03=12000 (05-01, 06-01 to 06-15,
set range from 0000 to 9999).
set 16-04=2 (CFM)
60% speed will be displayed as 120.0 CFM
20001–29999 □□. □□
100 % speed is 65.00ºC
Set 16-03=26500 (05-01, 06-01 to 06-15,
set range from 0000 to 9999)
Set 16-04=20 (ºC)
60% of speed is displayed as 39.00 ºC
30001- 9999 □. □□□
100 % speed is 2.555 m/s
Set 16-03=32555
Set 16-04=14 (m/s)
60% speed is displayed as 1.533 m/s
16- 05 LCD Backlight
Range
【0~7】
Adjust the screen contrast of the digital operator. If it is set to 0, the screen backlight is turned
off.