4-226
22- 10 PM SLV Start Current
Range 【20.0 ~ 200.0】%
22- 11 I/F Mode Start Frequency Switching Point
Range 【1.0 ~ 20.0】%
22- 14 Armature Resistance of PM Motor
Range 【0.001 ~ 30.000】Ω
22- 15 D-axis Inductance of PM Motor
Range 【0.01 ~ 300.00】mH
22- 16 Q-axis Inductance of PM Motor
Range 【0.01 ~ 300.00】mH
22-18 Flux-Weakening Limit
Range 【0 ~ 100】%
22- 21 PM motor tuning
Range
【0】: PM Motor Tuning is not Active
【1】: Parameter Auto-tune (for PMSLV Tuning)
22- 23 PM SLV acceleration time
Range 【0.1~10.00】 Sec
22- 25 Initial Position Detection of PM Motor
Range
【0】: Disable
【1】: Detected wheb inverter is running
PMSLV Start Current (22-10)
Set torque current at start and the unit is the percentage of motor rated current.
I/F Mode Start Frequency Switching Point (22-11)
This function is for the switching point from open-loop to close-loop in PMSLV mode. The unit is
percentage for rated speed of motor. It recommends that over 5% for 400V and over 10% for 200V.
Armature Resistance of PM Motor (22-14)
Set resistor for each phase of the motor in unit of 0.001Ω. It is set automatically when the motor
auto-tunes (22-21).
D-axis Inductance of PM Motor (22-15)
Set motors D-axis inductance in unit of 0.001mH. It is set automatically when the motor auto-tunes
(22-21).
Q-axis Inductance of PM Motor (22-16),
Set motors Q-axis Inductance in unit of 0.001mH. It is set automatically when the motor auto-tunes
(22-21).
Flux-Weakening Limit (22-18)
If the motors maximum rotation speed (22-05) is set to be higher than the motors rated rotation
speed (22-04), it will automatically start the flux-weakening control. It is set to limit the maximum
flux-weakening energy and the unit is the percentage of motor rated current.