AP 3-26
No. Object Name Description Unit Classification Range
AI8 Motor R-HP Motor rated power horsepower R
AI9 Motor R-RPM Motor rated rotation speed No Units R
AI10 Motor R-Hz Motor rated frequency Hz R
AI11 CarrierFreq Carrier frequency KiloHertz R 4-16
AI12 Comm Station INV communication station No Units R 1-254
AI13 BaudRate Baudrate setting No Units R 0-3
AI14 BacnetSel Communication mode selection No Units R 0-1
AI15 DevInstance Inverter number No Units R 1-254
Table 4 Analog output property list (Read/Write)
No. Object Name Description Unit Classification Range
AO0 Set frequency Frequency command Hz R/W 0-599
AO1 TB2 AO1 Analog output voltage 1 Volt R 0-10
AO2 - - - - -
AO3 Motor R-Amp Motor rated current Amps R/W 0-65535
AO4 PwrL Sel Momentary stop and restart selection No Units R 0-1
AO5 RestartSel Number of Fault Auto-Restart Attempts No Units R 0-10
AO6 RestartDelay Fault Auto-Restart Time seconds R 0-7200
AO7 FreqCommand1 Speed frequency setting-stage 0 Hz R/W 0-599
AO8 FreqCommand2 Speed frequency setting-stage 1 Hz R/W 0-599
AO9 FreqCommand3 Speed frequency setting-stage 2 Hz R/W 0-599
AO10 FreqCommand4 Speed frequency setting-stage 3 Hz R/W 0-599
AO11 FreqCommand5 Speed frequency setting-stage 4 Hz R/W 0-599
AO12 FreqCommand6 Speed frequency setting-stage 5 Hz R/W 0-599
AO13 FreqCommand7 Speed frequency setting-stage 6 Hz R/W 0-599
AO14 FreqCommand8 Speed frequency setting-stage 7 Hz R/W 0-599
AO15 FreqCommand9 Speed frequency setting-stage 8 Hz R/W 0-599
AO16 FreqCommand10 Speed frequency setting-stage 9 Hz R/W 0-599
AO17 FreqCommand11 Speed frequency setting-stage 10 Hz R/W 0-599
AO18 FreqCommand12 Speed frequency setting-stage 11 Hz R/W 0-599
AO19 FreqCommand13 Speed frequency setting-stage 12 Hz R/W 0-599
AO20 FreqCommand14 Speed frequency setting-stage 13 Hz R/W 0-599
AO21 FreqCommand15 Speed frequency setting-stage 14 Hz R/W 0-599
AO22 FreqCommand16 Speed frequency setting-stage 15 Hz R/W 0-599
AO23 RunMode Main run command source No Units R/W 0-2
AO24 ReverseOper Direction locked command No Units R/W 0-1
AO25 StoppingSel Stop modes selection No Units R/W 0-1
AO26 FrequenceComm Main frequency command source No Units R/W 0-5
AO27 FreqUpperLim Upper limit frequency Hz R/W 0-599
AO28 FreqLowerLim Lower limit frequency Hz R/W 0-598.99
AO29 Acc Time1 Acceleration time 1 seconds R/W 0-6000.0
AO30 Dec Time1 Deceleration time 1 seconds R/W 0-6000.0