4-17
Group 00 Basic Parameters
Code Parameter Name Setting Range Default Unit
Control mode
Attribute
V/F SLV
PM
SLV
00-00
Control Mode Selection
0:V/F
2:SLV
5:PMSLV
0 - O O O *3
00-01
Motor’s Rotation
Direction
0:Forward
1:Reverse
0 - O O O *1
00-02
Main Run Command
Source Selection
0:Keypad
1:External Terminal (Control Circuit)
2:Communication Control (RS-485)
3:PLC
1 - O O O
00-03
Alternative Run Command
Selection
0:Keypad
1:External Terminal (Control Circuit)
2:Communication Control (RS-485)
3:PLC
0 - O O O
00-04
Operation Modes For
External Terminals
0:Forward/Stop-Reverse/Stop
1:Run/Stop- Reverse/Forward
2:3 Wire Control Mode Run/Stop
0 - O O O
00-05
Main Frequency
Command
Source Selection
0:UP/DOWM of Keypad
1:Potentiometer on Keypad
2:External AI1 Analog Signal Input
3:External AI2 Analog Signal Input
4:External Up/Down Frequency
5:Communication Setting Frequency
6:Reserved
7:Pulse Input(*6)
2 - O O O
00-06
Alternative Frequency
Command Source
Selection
0:UP/DOWM of Keypad
1:Potentiometer on Keypad
2:External AI1 Analog Signal Input
3:External AI2 Analog Signal Input
4:External Up/Down Frequency
5:Communication Setting Frequency
6:Reserved
7:Pulse Input(*6)
0 - O O O
00-07
Main and Alternative
Frequency Command
Modes
0:Main or Alternative Frequency
1:Main Frequency+ Alternative
Frequency
0 - O O O
00-08
Communication
Frequency Command
0.00~599.00
0.00 Hz O O O *4
00-09
Frequency Command
Save on Power Down
0:Disable
1:Enable
0 - O O O