4-22
Group 03 External Digital Input and Output Parameters
Code Parameter Name Setting Range Default Unit
Control mode
Attribute
V/F SLV
PM
SLV
03-06
Up/Down frequency
step
0.00~5.00 O O O
03-07
Up/Down Keep
Frequency Status after
Stop Command
0:When Up/Down is used, the preset frequency
is held as the inverter stops, and the UP/Down
function is disabled
1:When Up/Down is used, the preset frequency
is reset to 0 Hz as the inverter stops.
2:When Up/Down is used, the preset frequency
is held as the inverter stops, and the UP/Down
is available.
3:When acceleration is used, the output
frequency will be updated.
0 - O O O
03-08
S1~S6 DI scan Time
1~200 1 ms O O O
03-09
Multi-Function
Terminal S1~ S4 type
selection
xxx0b:S1 A Contact, xxx1b:S1 B Contact
xx0xb:S2 A Contact, xx1xb:S2 B Contact
x0xxb:S3 A Contact, x1xxb:S3 B Contact
0xxxb:S4 A Contact, 1xxxb:S4 B Contact
0000b - O O O
03-10
Multi-Function
Terminal S5~ S6 type
selection
xxx0b:S5A Contact, xxx1b:S5 B Contact
xx0xb:S6 A Contact, xx1xb:S6 B Contact
0000b - O O O
03-11
Relay (R1A-R1C)
Output
0:During Running
1
-
-
O O O
1:Fault Contact Output O O O
2:Frequency Agree O O O
3:Setting Frequency Agree (03-13±03-14) O O O
4:Frequency Detection 1 (≧03-13+03-14) O O O
5:Frequency Detection 2 (≦ 03-13+03-14) O O O
6:Automatic Restart O O O
7:Momentary AC Power Loss
O
O O
8:Rapid Stop
O
O O
9:Base Block O O O
10:Motor Overload Protection (OL1)
O
O O
11:Drive Overload Protection (OL2)
O
O O
12:Over-torque Threshold Level (OL3) O O O
13:Preset Output Current Reached O O O
14:Brake Control O O O
15:PID Feedback Signal Loss
O
O O
16:Single pre-set count (3-22~23)
O O O
17:Dual pre-set count (3-22~23)
O
O O
18:PLC Status Indicator (00-02) O O O
19:PLC control * O O O
20:Zero Speed O O O
30:Motor 2 Selection
O X X