4-23
Group 03 External Digital Input and Output Parameters
Code Parameter Name Setting Range Default Unit
Control mode
Attribute
V/F SLV
PM
SLV
37:Detection Output of PID Feedback Loss
54:Turn on short-circuit braking
55:Low Current Detection
59:OH Detection
O O O
X X O
03-12
Relay (R2A-R2B)
Output
0 -
O O O
O O O
03-13
Frequency Detection
Level
0.0~599.0
0.0 Hz O O O
03-14
Frequency Detection
Width
0.1~25.5
2.0 Hz O O O
03-15
Current Agree Level 0.1~999.9
0.1 A O O O
03-16
Delay Time of Current
Agree Detection
0.1~10.0
0.1 s O O O
03-17
* Mechanical Braking
Release Level
0.00~20.00
0.00 Hz O O O
03-18
* Mechanical Braking
Level Set
0.00~20.00 0.00 Hz O O O
03-19
Relay (R1A-R2B) Type
xxx0b:R1 A Contact, xxx1b:R1 B Contact
0000b - O O O
xx0xb:R2 A Contact, xx1xb:R2 B Contact
03-20
Internal / External
Multi-Function Input
Terminal Selection
0~63 0 O O O
03-21
Action To Set The
Internal
Multi-Function Input
Terminals
0~63 0 O O O
03-22 Pre-Set Count 1 0~9999 0 O O O
03-23 Pre-Set Count 2 0~9999 0 O O O
03-24
Output Under Current
Detection
0:Invalid
0 O O O
1:Valid
03-25
Output Under Current
Detection Level
0~999.9 0.1 A O O O
03-26
Output Under Current
Detection Delay Time
0.0~655.34s 0.01 s O O O
03-27 Pulse Frequency 50~25000 200 Hz O O O *1
03-28 Pulse Input Gain 0.0~1000.0 100.0 % O O O *1
03-30
Selection of Pulse
Input
0:General Pulse Input
0 - O O O
1:PWM
03-33 Pulse Input Bias -100.0~100.0 0.0 % O O O *1
03-34
Filter Time of Pulse
Input
0.00~2.00 0.1 s O O O *1
03-53 Current Agree Level 2 0.0~999.9 0.1 A O O O
*:If the maximum output frequency of motor is over 300HZ, the frequency resolution is changed to 0.1Hz