EasyManua.ls Logo

TECO E510s Series - Page 90

TECO E510s Series
425 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4-24
Group 04 Analog signal inputs / Analog output
Code Parameter Name Setting Range Default Unit
Control mode
Attribute
V/F SLV
PM
SLV
04-00 Analog Input Signal Type
0:AI1 0~10V
AI2 0~10V / 0~20mA
1AI1 0~10V
AI2 4~20mA / 2~10V
2AI1 2~10V
AI2 0~10V / 0~20mA
3AI1 2~10V
AI2 4~20mA / 2~10V
1 - O O O
04-01
AI1 Signal Scanning and
Filtering Time
0.00~2.00 0.03 s O O O
04-02 AI1 Gain 0.0~1000.0 100.0 % O O O *1
04-03 AI1 Bias -100.0~100.0 0 % O O O *1
04-05 AI1 Slope
0:Positive
1:Negative
0 - O O O
04-06
AI2 Signal Scanning and
Filtering Time
0.00~2.00 0.03 s O O O
04-07 AI2 Gain 0.0~1000.0 100.0 % O O O *1
04-08 AI2 Bias -100.0~100.0 0 % O O O *1
04-10 AI2 Slope
0:Positive
1:Negative
0 - O O O
04-11 Analog Output (AO) Mode
0:Output Frequency
1:Frequency Command
2:Output Voltage
3:DC Bus Voltage
4:Output Current
0 -
O O O
O O O
O O O
O O O
O O O
04-12 AO Gain 0.0~1000.0 100.0 % O O O *1
04-13 AO Bias -100.0~100.0 0 % O O O *1
04-15 AO Slope
0:Positive
1:Negative
0 - O O O
04-16 F-Gain
0:Disable
1:Enable
0 - O O O
04-20
AO Signal Scanning and
Filtering Time
0.00~0.50 0.00 s O O O *1
04-22 AO voltage correction
0:Disable
1:Enable
0 - O O O

Table of Contents

Other manuals for TECO E510s Series

Related product manuals