4-30
Group 07 Start/Stop Parameters
Code Parameter Name Setting Range Default Unit
Control mode
Attribute
V/F SLV
PM
SLV
07-00
Momentary Power Loss and
Restart
0:Disable
1:Enable
0 - O O X
07-01
Fault Reset Time
0~7200
0 sO O O
07-02
Number of Auto Restart
Attempts
0~10
0 -O O O
07-03
Reset Mode Setting
0:Enable Reset Only when Run
Command is Off
1:Enable Reset when Run
Command is On or Off
0 -O O O
07-04
Momentary Power Loss and
Restart
0:Enable Direct run on power up
1:Disable Direct run on power up
1 -O O O
07-05
Delay-ON Timer 1.0~300.0
1.0 sO O O
07-06
DC Injection Braking Start
Frequency
0.0~10.0
1.5 Hz O O O
07-07
DC Injection Braking Level
(Current Mode)
0~100
50 %O O O
07-08
DC Injection Braking Time 0.00~100.00
0.50 s O O O
07-09
Stop Mode Selection
0:Deceleration to Stop
1:Coast to Stop
2:DC Braking Stop in All Fields
3:Coast to Stop with Timer
0 - O O X
07-10
Speed Search Mode Selection
0:Normal Start
1:Execute Speed Search Once
2:Speed Search Start
0 -O O O
07-13
Low Voltage Detection Level
200V:100~300
190
VO O O
400V:250~600
380
07-15
DC Injection Brake Mode
0:Current Mode
1:Voltage Mode
1 O O O
07-16
DC Injection Braking Time at
Start
0.00~100.00
0.00 s O O O
07-18
Minimum Base block Time 0.1~5.0
KVA s O O O
07-19
Speed Direction Search
Operation Current
0~100
50 % O O X
07-20
Speed Search Operating Current 0~100
20 % O O X
07-21
Integral Time of Speed
Searching
0.1~10.0
2.0 s O O X
07-22
Delay Time of Speed Searching 0.0~20.0
0.2 s O O X
07-23
Voltage Recovery Time
0.1~5.0 2.0 s O O X
07-24
Direction-Detection Speed
Search Selection
0:Invalid
1 - O O X
1:Valid
07-25
Low Voltage Detection Time
0.00~1.00 0.02 s O O O