EasyManua.ls Logo

TECO E510s Series - Page 96

TECO E510s Series
425 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4-30
Group 07 Start/Stop Parameters
Code Parameter Name Setting Range Default Unit
Control mode
Attribute
V/F SLV
PM
SLV
07-00
Momentary Power Loss and
Restart
0:Disable
1:Enable
0 - O O X
07-01
Fault Reset Time
0~7200
0 sO O O
07-02
Number of Auto Restart
Attempts
0~10
0 -O O O
07-03
Reset Mode Setting
0:Enable Reset Only when Run
Command is Off
1:Enable Reset when Run
Command is On or Off
0 -O O O
07-04
Momentary Power Loss and
Restart
0:Enable Direct run on power up
1:Disable Direct run on power up
1 -O O O
07-05
Delay-ON Timer 1.0~300.0
1.0 sO O O
07-06
DC Injection Braking Start
Frequency
0.0~10.0
1.5 Hz O O O
07-07
DC Injection Braking Level
(Current Mode)
0~100
50 %O O O
07-08
DC Injection Braking Time 0.00~100.00
0.50 s O O O
07-09
Stop Mode Selection
0:Deceleration to Stop
1:Coast to Stop
2:DC Braking Stop in All Fields
3:Coast to Stop with Timer
0 - O O X
07-10
Speed Search Mode Selection
0:Normal Start
1:Execute Speed Search Once
2:Speed Search Start
0 -O O O
07-13
Low Voltage Detection Level
200V:100~300
190
VO O O
400V:250~600
380
07-15
DC Injection Brake Mode
0:Current Mode
1:Voltage Mode
1 O O O
07-16
DC Injection Braking Time at
Start
0.00~100.00
0.00 s O O O
07-18
Minimum Base block Time 0.1~5.0
KVA s O O O
07-19
Speed Direction Search
Operation Current
0~100
50 % O O X
07-20
Speed Search Operating Current 0~100
20 % O O X
07-21
Integral Time of Speed
Searching
0.1~10.0
2.0 s O O X
07-22
Delay Time of Speed Searching 0.0~20.0
0.2 s O O X
07-23
Voltage Recovery Time
0.1~5.0 2.0 s O O X
07-24
Direction-Detection Speed
Search Selection
0:Invalid
1 - O O X
1:Valid
07-25
Low Voltage Detection Time
0.00~1.00 0.02 s O O O

Table of Contents