4-31
Group 07 Start/Stop Parameters
Code Parameter Name Setting Range Default Unit
Control mode
Attribute
V/F SLV
PM
SLV
07-26
Start-up Mode Selection of SLV
Coast to Stop
0:Start With Speed Search
1:Normal Start
0 - X O X
07-27
Start Selection after Fault During
SLV Mode
0:Start With Speed Search
1:Normal Start
0 - X O X
07-28
Start after External BaseBlock
0:Start With Speed Search
1:Normal Start
0 - O O X
07-29
Run Command Selection at the
Action of DC Braking
0:Not Allowable to Run
1:Allowable to Run
0 - O X X
07-33
Start Frequency of Speed Search
Selection
0:Maximum Output Frequency
1:Frequency Command
0 - O O X
07-34
Start Short-Circuit Braking Time
0.00~100.00 0.00 s X X O
07-35
Stop Short-Circuit Braking Time
0.00~100.00 0.50 s X X O
07-36
Short-Circuit Braking Current
Limited
0.0~200.0 100.0 % X X O
07-37
Pre-Excitation Time
0.00~10.00 2.00 s X O X
07-38
Pre-Excitation Level
50~200 100 % X O X
07-39
Short-Circuit Braking Time of
PM Motor Speed Search
Function
0.00~100.00 0.00 s X X O
07-40
DC Injection Braking Time of PM
Motor Speed Search Function
0.00~100.00 0.00 s X X O
07-45
STP2 function selection
0:STP2 is enabled
1:STP2 is disabled
0 O O O
* :If the maximum output frequency of motor is over 300HZ, the frequency resolution is changed to 0.1Hz