Group 08 Protection Parameters
Code Parameter Name Setting Range Default Unit
Control mode
Attribute
V/F SLV
PM
SLV
08-14
Selection of
Over-Torque Action
0:Deceleration to Stop when Over Torque is
Detected.
1:Display Warning when Over Torque is
Detected. Go on Operation.
2:Coast to Stop when Over Torque is Detected
0 - O O O
08-15
Level of Over-Torque
Detection
0~300 160 % O O O
08-16
Time of Over-Torque
Detection
0.0~10.0 0.1 s O O O
08-21
Limit of Stall Prevention
During Acceleration
1~100 50 % O O O
08-22
Stall Prevention
Detection Time During
Run
2~100 100 ms O O O
08-23
Ground Fault (GF)
Selection
0:Disable
1:Enbale
0 - O O O
08-24
Operation Selection of
External Fault
0:Deceleration to Stop
1:Coast to Stop
2:Continuous Operation
0 - O O O
08-25
Detection Selection of
External Fault
0:Immediately Detect When the Power is
Supplied
1:Start to Detect during Operation
0 - O O O
08-35
Motor Overheating
Fault Selection
0:Disable
1:Deceleration to Stop
2:Coast to Stop
3:Keep Running
0 - O O O
08-36
PTC Input Filter Time
Constant
0.00 ~ 5.00 2.00 s O O O
08-38 Delay Time of Fan Off 0~600 60 s O O O
08-39
Delay Time of Motor
Overheat Protection
1~300 60 s O O O
08-40
Motor2 Acceleration
Stall Prevention Level
20~200
HD: 150
% O O X
ND: 120
08-41
Motor2 Acceleration
Stall Prevention Limit
1~100 50 % O O X
08-42 PTC Protection Level 0.1~10.0V 0.7 V O O O
08-43 PTC Restart Level 0.1~10.0V 0.3 V O O O
08-44 PTC Warning Level 0.1~10.0V 0.5 V O O O
08-46
Temperature Agree
Level
0~254°C 0
°C O O O
08-47
Temperature Reset
Level
0~254°C 0
°C O O O