7-40
Cn036 ID Setting
【
8-1
】
Initial Value Unit Setting Range Effective Cn029 Reset
1 -- 1 ~ 254
★
--
RS-485 CANopen EtherCAT Pi Pe Pt S T
0027H 2024H 2024H O O O O O
Setting Description: When using the Modbus Communication Interface, each set of Drivers needs to set different IDs in
this parameter in advance; if the IDs are set repeatedly, it will result in communication not being
operated normally.
Cn037.0
Modbus RS-485 Communication Transmission Rate
【
8-1
】
Initial Value Unit Setting Range Effective Cn029 Reset
1 -- 0 ~ 5
★
--
RS-485 CANopen EtherCAT Pi Pe Pt S T
0028H 2025H 2025H O O O O O
Setting Description:
Setting Description Setting Description
0 4800 bps 3 38400 bps
1 9600 bps 4 57600 bps
2 19200 bps 5 115200 bps
Cn037.2 RS-485 Communication Write Selection
【
8-1
】
Initial Value Unit Setting Range Effective Cn029 Reset
1 -- 0 ~ 1
★
--
RS-485 CANopen EtherCAT Pi Pe Pt S T
0028H 2025H 2025H O O O O O
Setting Description:
Setting Description
0 RS-485 Communication Write to EEPROM
1 RS-485 Communication Write to SRAM
Cn038.0 Protocol
【
8-1
】
Initial Value Unit Setting Range Effective Cn029 Reset
0 -- 0 ~ 8
★
--
RS-485 CANopen EtherCAT Pi Pe Pt S T
0029H 2026H 2026H O O O O O