4-24
Maximum output Frequency
Set frequency
Acc-time 00-14
Dec-time 00-15
Actual acc-time
Actual dec-time
Hz
T0
The minimum starting
frequency
Note:
Maximum output frequency fixed when VF curve (01-00) is set to a value of 1 to 6.
Maximum output frequency parameter 01-02 can be adjusted when VF curve (01-00) is set to 7.
00-18
Jog Frequency
Range
1.00~25.00Hz
00-19
Jog Acceleration Time
Range
0.1~3600.0s
00-20
Jog Deceleration Time
Range
0.1~3600.0s
The JOG function is active when any of the multi-function input terminals S1 to S5 parameters 03-00~03-04
is set to 6JOG FWD or7JOG REV. Refer to parameter group 3.