4-25
01-V/F command group
01-00
Volts/Hz Patterns (V/F)
Range
1~7
Set 01-00 to one of the following preset V/f selections1~6based on the application.
Parameters 01-02~01-09 are automatically set (read-only) when 01-00 is set to a value from 1 to 6.
Six fixed V/f patterns are shown below.1~3for 50 Hz motor and4~6for 60 Hz motors.
TYPE
50Hz
60Hz
Function
01-00
V/F pattern
01-00
V/F pattern
General Use
=1
100
B
C
1 2.5 50
(V)%
Hz
650
=4
100
B
C
1 3.0 50
(V)%
Hz650
High start torque
=2
100
B
C
1 2.5 50
(V)%
Hz650
=5
100
B
C
1 3.0 50
(V)%
Hz650
Decreasing torque
=3
100
B
C
1 25 50
(V)%
Hz650
=6
100
B
C
1 30 50
(V)%
Hz650