EasyManua.ls Logo

TELEDYNE OLDHAM SIMTRONICS iTRANS 2 - 6 Modbus Interface; 6.1 Modbus Interface Overview

TELEDYNE OLDHAM SIMTRONICS iTRANS 2
84 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
iTRANS 2
FIXED POINT SINGLE OR DUAL GAS MONITOR
WITH DUAL ANALOG OUTPUTS
USER MANUAL
77036429-EN
Revision 7.0
35
6 Modbus Interface
6.1 Introduction
IMPORTANT:
The
device with public Modbus
interface can also be configured to operate with a MX43
controller from TELEDYNE OLDHAM SIMTRONICS. Please
follow the procedure given below to enable MX43-
compatibility mode on .
Set the Modbus ID of using dip-switches as shown in
Figure 4-10 according to MX43 configuration (for details
please see the user manual of MX43 controller). The MX43-
compatibility menu on is pass
word protected. To
enter MX43-compatibility menu, remove the front cover of
and press “Enter” key. The access code is “Enter”,
“Up”, “Down”, “Up”, “Mode”.
Figure 6-1 MX43-compatibilty
Menu
Once the correct access code has been entered then the user can select to enable (1) or disable
(0) the MX43-compatibility mode on using “Up” or “Down” key then the selection is
confirmed by pressing the “Enter” key.When programming the ModBus ID address on the
electronics module or on the smart sensor board, use the binary reference chart on the following
page. A “1” represents “ON” on the switch bank, and position 1 of the switch bank represents
the right most binary digit (LSB). ModBus characteristics for the are listed below.
Characteristic
Description
Hardware
2-wire mode (not 4-wire)
Baud Rate
9600
Electrical Standard TIA/EIA-485
Transmission Mode
RTU mode (not ASCII)
Message Coding System 8-bit
Start Bits
1
Data Bits
8 (LSB sent first)
Parity Bits 0
Stop Bits
1
Table 6-1 ModBus Characteristics for the Gas Monitor

Related product manuals