Appendix E Factory Default Settings
This appendix lists factory default settings based on the individual sensor(s) used. Refer
to Table E - 1.
Sensor Name Range Resolution Cal Gas
Default Low
Alarm
Default High
Alarm
2
SO
2
0-99.9 ppm 0.1 ppm 5 ppm 2.0 ppm 4.0 ppm
NO
2
0-99.9 ppm 0.1 ppm 5 ppm 1.0 ppm 2.0 ppm
Cl
2
0-99.9 ppm 0.1 ppm 10 ppm 0.5 ppm 1.0 ppm
2
PH
3
0-1.00 ppm 0.01 ppm 1.0 ppm 0.30 ppm 0.60 ppm
CO/H
2
NULL 0-999 ppm 1 ppm 100 ppm 35 ppm 70 ppm
NO 0-999 ppm 1 ppm 25 ppm 25 ppm 50 ppm
NH
3
0-500 ppm 1 ppm 25 ppm 25 ppm 50 ppm
2
O
2
0-30% Vol. 0.1% Vol. 20.9% 19.5% 23.5%
Infrared, LEL 0-100% LEL 1% LEL 50% LEL 10% LEL 20% LEL
Catalytic Bead,
LEL Methane
0-100% LEL 1% LEL 50% LEL 10% LEL 20% LEL
LEL Pentane
0-100% LEL 1% LEL 25% LEL 10% LEL 20% LEL
CO
2
0-0.05% Vol. 0.01% Vol. 0.25%Vol. 0.10% Vol 0.20% Vol
CO
2
0-5.00% Vol. 0.01% Vol. 2.50% Vol. 1.00% Vol 2.00% Vol
CO
2
0-100% Vol. 1% Vol. 50% Vol. 10% Vol 20% Vol
Table E - 1 Factory Default Settings