Thermokon Sensortechnik GmbH Seite 21
5 RS485 Modbus Register-Specification
The register assignment of all Modbus-capable NOVOS devices is uniformly structured. Depending on the product and version, certain registers are not
used. Unused or empty registers are written with the value -1 by default.
All configuration registers (except 1106-1111) are written into the EEROM of the device.
The following data blocks contain configuration options and functions of the entire NOVOS family.
5.1 Data block “Favourites”
With the help of the favourite registers, the user can create his own project-specific register structure. Favourite registers are links or
duplicates of already existing registers. Especially for small projects (with e.g. only one light circuit and/or two blinds), not all registers
need to be queried by the BMS, but only a few favourite registers are required. The advantage is the significantly shorter reading times
per device.
The individual assignment is made through the configuration registers from register 5000 ff.
Example: If register 5000 contains the value 103, the effective setpoint is provided in favourite register 1. If register 5001 contains the
value 500, the temperature reading is provided in favourite register 2.
Parameter Description N3 N5 N7
Touch/
EVO
Min Max Default Access
Assignment see register 5000
● ● ● ●
0
Assignment see register 5001
● ● ● ●
1
Assignment see register 5002
● ● ● ●
2
Assignment see register 5003
● ● ● ●
3
Assignment see register 5004
● ● ● ●
4
Assignment see register 5005
Assignment see register 5006
● ● ● ●
6
Assignment see register 5007
● ● ● ●
7
Assignment see register 5008
● ● ● ●
8
Assignment see register 5009
● ● ● ●
9
Assignment see register 5010
● ● ● ●
10
Assignment see register 5011
● ● ● ●
11
● ● ● ●
Assignment see register 5099 ● ● ● ●
99
To reduce further bus accesses to the NOVOS Touch room operating unit, polling sequences can be suspended when the room
operating unit is not being operated. Every touch on the touch screen is recognised and saved. The detected interaction can be reset
manually by the BMS or automatically after a set time.
Parameter Description N3 N5 N7
Touch/
EVO
Min Max Default Access
Touchdisplay wurde berührt
1 = Interaktion erkannt
0 = keine Interaktion (Reset nach
● 0
r / w
uint16_t
197
Rückstellzeit nach erkannter
Interaktion
Zeit nach der Datenadresse 197
zurückgesetzt wird. 0 deaktiviert die
Rückstellzeit – Datenadresse 197
muss in diesem Fall von der GLT
zurückgeschrieben werden.
● 0
r / w
uint16_t
4008