5.3 Data block “Lighting”
Parameter Description N3 N5 N7
Touch/
EVO
Min Max Default Access
Data
address
Coil mapping
Status of lighting 1-8
Status Scenes 1-8
Coil states ON/OFF (chapter 7.1 & 7.2)
of lighting and scenes (bit-coded)
bit 0 - bit 7 = lighting 1-8
bit 8 - bit 15 = scenes 1-8
r / w
uint16_t
199
Lighting status 1
Depending on the configuration in
register 1416, the action of the user is
provided.
Details in register 1416.
The Light ON/OFF state is output in coils
0-7. See coil data block "Light" (chapter
7.1).
0..100 = Dimm_Value
110 = Button_No_Press
111 = Button_Short_Press_UP
112 = Button_Long_Press_UP
113 = Button_Short_Press_DOWN
114 = Button_Long_Press_DOWN
115 = Button_Pressed_UP
116 = Button_Pressed_DOWN
0 116
0
r / w
uint16_t
200
Lighting status 2
201
Lighting status 3
202
Lighting status 4
203
Lighting status 5
204
Lighting status 6
205
Lighting status 7
206
Lighting status 8
207
AUTO Mode
for Lighting 1-8
Summary of coils 32-39
If individual lighting circuits are to be
controlled temporarily exclusively by the
BMS, the buttons for setting individual
lighting circuits can be disabled.
All the buttons on the user interface are
greyed out.
Lighting 1-8 (binary coded)
bit 0 = Buttons Lighting 1
bit 1 = Buttons Lighting 2
bit 7 = Buttons Lighting 8
0 = AUTO-Mode OFF
1 = AUTO-Mode ON (Buttons locked)
0 255 0
r / w
uint16_t
208
The following register block describes the RGB(W) values of the colour picker (colour mixer) or the color temperature of the color temperature picker.
RYB(W) Value
or color temperature
(according to setting, Data
address 1416)
Lighting 1
Red value 0..255
or color temperature 0..15.000 K
0 15000
r / w
uint16_t
210
Green-value 0..255
0 255
r / w
uint16_t
211
Blue value 0..255
0 255
r / w
uint16_t
212
White value 0..255
0 255
r / w
uint16_t
213
RYB(W) Value
or color temperature
(according to setting, Data
address 1542)
Lighting 8
Red value 0..255
or color temperature 0..15.000 K
0 15000
r / w
uint16_t
238
Green value 0..255
0 255
r / w
uint16_t
239
Blue value 0..255
0 255
r / w
uint16_t
240
White value 0..255
0 255
r / w
uint16_t
241