Manual NOVOS und thanos EVO
Thermokon Sensortechnik GmbH Seite 33
6.5 Configuration data block “Lighting”
Up to 8 different light circuits can be operated and parameterized.
Parameter Description N3 N5 N7
Touch/
EVO
Min Max Default Access
Data
address
Display lighting menu
(Display ON/OFF)
Display lighting menu in the menu bar
0 = no
● ● 0 1 1 r / w 1400
Number of adjustable lighting circuits
0…8
● ● 0 8 8 r / w 1401
Graphical representation of
the lighting circuits
With NOVOS Touch and thanos EVO
this function can be displayed via the
corresponding submenu and/or via a
2D room graphic
0 = List view
1 = 2D Floor plan view
● 0 2 0 r / w 1402
Name for the first lighting circuit
Max. 12 characters. One character in
Unicode format per register
● ● Light 1 r / w 1403..1414
Selection of the icon for
Lighting 1
0 = Universal light bulb
1 = Spot
2 = Light-cassette
3 = Floor lamp
● ● 0 105 0 r / w 1415