Seite 26 Thermokon Sensortechnik GmbH
5.6 Data block “Sensors”
Parameter Description N3 N5 N7
Touch/
EVO
Min Max Default Access
Data
address
Temperature
Configuration of the sensor
parameters
see Register block 2010 ff.
r
int16_t
500
rel. Humidity
Configuration of the sensor
parameters
see Register block 2110 ff.
r
int16_t
501
abs. Humidity
Configuration of the sensor
parameters
see Register block 2210 ff.
r
int16_t
502
Enthalpy
Configuration of the sensor
parameters
see Register block 2310 ff.
r
int16_t
503
Dew point
Configuration of the sensor
parameters
see Register block 2410 ff.
r
int16_t
504
CO2
Configuration of the sensor
parameters
see Register block 2510 ff.
r
int16_t
505
VOC
Configuration of the sensor
parameters
see Register block 2610 ff.
r
int16_t
506
CO2 / VOC MIX
Configuration of the sensor
parameters
see Register block 2710 ff.
r
int16_t
507
ext. Sensor 1
Configuration of the sensor
parameters
see Register block 2809 ff.
r/w
int16_t
508
ext. Sensor 2
Configuration of the sensor
parameters
see Register block 2909 ff.
r/w
int16_t
509
ext. Sensor 3
Configuration of the sensor
parameters
see Register block 3009 ff.
r/w
int16_t
510
ext. Sensor 4
Configuration of the sensor
parameters
see Register block 3109 ff.
r/w
int16_t
511
atm. air pressure
Configuration of the sensor
parameters
see Register block 3210 ff.
r
int16_t
512
Sensor error
Information, if an internal sensor
failure is detected
Sensor failure is bit-coded:
Bit 0 = Temp_rH
Bit 1 = Temp
Bit 2 = VOC
Bit 3 = CO2
r
uint16_t
513
Status of digital input
Connection to terminal 7
0 = open
1 = closed
r
uint16_t
514