- 49 -
(14)
Auto Start Configuration
Auto Start Delay (Default = 10 seconds)
Pre Heat Time (Default = 0 seconds)
Crank Time (Default = 10 seconds)
Crank Rest Time (Default = 10 seconds)
Warm Up Speed (Default = 800 rpm)
Warm Up Time (Default = 10 seconds)
Prime Speed (Default = 1000 rpm)
Prime Time (Default = 10 seconds)
Cool Down Speed (Default = 800 rpm)
Cool Down Time (Default = 10 seconds)
Crank Cycles (Default = 5)
Fault Bypass Period (Default = 10 seconds)
Crank Hold Delay (Default = 0)
Crank Release Speed (Default = 400 rpm)
Crank Hold Delay (Default = 0 TSec.)
(15)
Battery Recharge Configuration
Recharge Monitor (Default = Off)
Recharge Voltage Selection
Recharge Delay Selection
Recharge Run Time Selection
Next Recharge Time Interval Selection
(16)
Maintenance Configuration
Service Messages (Default = No)
Reset Interval Yes/No
Service Warning at: (Default = 0 Hrs.)
Service Requires At: (Default = 0 Hrs.)
Next Service Warning Interval (Default = 200 Hrs.)
Next Service Required Interval (Default = 250 Hrs.)
1
st
Service Warning Interval (Default = 75 Hrs.)
1
st
Service Required Interval (Default = 100 Hrs.)
(17)
Emissions Configuration
DEF Level Check
Low DEF Pre Alarm
Low DEF Alarm
DEF Alarm Delay
Allow Service Regen Yes/No (Deere Only)
Regen Interlock On/Off
TSC Transmit Yes/No (stop TSC to engine during regen)
DPF Inhibit Lamp Source