EasyManuals Logo

Thytronic SIF5600 User Manual

Thytronic SIF5600
96 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #10 background imageLoading...
Page #10 background image
10
10
SIF5600 - Manual - 03 - 2008
Reference standards EN60255-22-5 IEC61000-4-5
High energy surge:
- open circuit voltage (1.2/50 ms,
Ri=2 W) 4 kV
- short circuit current (8/20 ms) 400 A
- Uaux common mode (10 W, 9 mF)
2 kV
- Uaux differential mode (0 W, 18 mF)
1 kV
- I/O circuits common mode( 40 W, 0.5 mF)
2 kV
- I/O circuits differential mode (40 W, 0.5 mF)
1 kV
Reference standards EN60255-22-6 IEC61000-4-6
Conducted RF:
- 0.15...80 MHz AM 80% 1kHz 10 V
Reference standards IEC61000-4-8
Power frequency magnetic field
- 50 Hz continuous
100 A/m
- 50 Hz 1 s 1 kA/m
Reference standards EN61000-4-9 IEC61000-4-9
Pulse magnetic field
- generator (16.4/16 ms, 1000A) 1000 A/m
Reference standards EN61000-4-10 IEC61000-4-10
Damped magnetic field
- damped wave 0.1 MHz
100 A/m
- damped wave 1 MHz 100 A/m
Reference standards EN61000-4-12 IEC61000-4-12
Oscillatory waves
- damped oscillatory wave 0.1 MHz 2.5 kV
- damped oscillatory wave 1 MHz 1.0 kV
- common mode ring wave 2.0 kV
- differential mode ring wave 1.0 kV
Reference standards EN6100-4-16
Common mode disturbances in the frequency range 0 Hz...150 kHz
- dc voltage 30 V
- 50 Hz continuous 30 V
- 50 Hzr 1 s 300 V
- 0.015...150 kHz 30 V
Emission tests
Reference standards EN61000-6-4 (ex EN50081-2) EN55022 EN60255-25
- conducted emission (auxiliary power supply) 0.15...0.5 MHz 79 dB mV
0.5...30 MHz 73 dB mV
- radiated emission
30...230 MHz 40 dB mV/m
230...1000 MHz 47 dB mV/m
Climatic tests
Reference standards IEC60068-2 ENEL R CLI 01 CEI 50
Mechanical tests
Reference standards EN60255-21-1 EN60255-21-2 RMEC01
Vibration, shock and seismic vibration
-
EN60255-21-1 vibration (sinusoidal) Classe 1
- EN60255-21-2 shock Classe 1
Safety
Reference standards EN61010-1
- pollution degree 3
Rated insulation voltage 250V
Overvoltage category III
High voltage test 50Hz 2 kV 60s
Impulse voltage withstand (1.2/50
ms)
5 kV
Other standards
- Electrical relays EN61810-1 (ex CEI 41-1)
IEC 60255
- Climatic and mechanical CEI 50
IEC 60068
- protection degree (IP code) EN60529, EN60529/A1
- CE conformity 89/336/EEC
- Low voltage 73/23/EEC

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Thytronic SIF5600 and is the answer not in the manual?

Thytronic SIF5600 Specifications

General IconGeneral
BrandThytronic
ModelSIF5600
CategoryRelays
LanguageEnglish

Related product manuals