Viewing example of the Event 1 data:
Info Events stored (number of stored events)
Last event (event for which the last recording has been stored)
Event1 E1 Reading Direct (Type of reading, e.g.: Direct)
E1 IL1r 15.424 A/In (L1 phase current value)
E1 IL2r 15.424 A/In (L2 phase current value)
E1 IL3r 15.424 A/In (L3 phase current value)
E1 IEr 0.00000 A/In (Residual current value)
E1 Cause Trip I> (function responsible for the trip)
E1 Phases (phases on which the current was detected)
(1)
E1 Blin1r Off (Block input status)
E1 Blout1-2rr Off (Block output status)
E1 Year 2000 Year (2000) of recording of event 1
E1 Month 1 Month (January) of recording of event 1
E1 Day 1 Day of recording of event 1
E1 Hour 1 Hour of recording of event 1
E1 Minute 55 Minute of recording of event 1
E1 Second 23 Second of recording of event 1
E1 Millisecond 61 Millisecond of recording of event 1
Event2 E2 Reading ......................
.....................
Note: b
y positioning the cursor on the value of the variable (Value field), and clicking it is possible to obtain additional information; for example in the
case of values viewed in hexadecimal notation it is possible to analyze the message:
Phases 0001 hex
Note: by means of the command described, it is possible to view the phase or phases in which the current has exceeded the threshold (0001 hex
corresponds to phase L1)
Info
The following information concerning the SIF5600 relay are available:
Identification 5 ID of the SIF5600 digital protection relay
Serial number 1234 Serial number of the SIF5600 digital protection relay
FW Release 200 Firmware version (this means 2.00)
Protocol Release 101 Protocol version (this means 1.01)
Mean elab cycle 556
ms
mean processing cycle duration in microseconds Max elab. cycle
Max elab cycle 2400 ms
max processing cycle duration in microseconds
Stack load 60 % stack occupation
Warm reset number 2400 ms
number of internal resets
Frequency 50.00 Hz measurement of the power frequency