READING AND MODIFYING SETTINGS (Set)
Inside the Set sub-menù it is possible to display and/or change the setting data.
SET
Relays
50 - 51
50N - 51N
52
Block
Clear (present in the display menu and absent on the
ThySetter)
Store
Base
Setting the measurement reading mode:
Inp value 200 Setting the phase CT nominal primary current
Inp unit A Setting the phase CT primary current unit
IEnp value 100 Setting the core balance CT primary current
IEnp unit A Setting the core balance CT primary current unit
Reading Direct Setting the reading mode of the currents, in primary Amperes
Relays
It is possible to select the mode of operation and the assignment of the output relays to the protec-
tion functions.
T
he operation of each output relay is determined by the normal resting condition with the relay
de-energized or energized and on the method of resetting, automatic or manual (NON LATCHED or
LATCHED).
Relays assigned to the self-test function are automatically set as normally ENERGIZED with auto-
matic reset (NO
T LATCHED); this mode of operation may not be altered.
Output relays K1...K4 may be assigned to one or more of the following functions:
- Self test
(self-test function)
- PW break Blin1 (Blin1 pilot wire breakage),
- CB fail (breaker failure),
- PW shorted (pilot wire short-circuit),
- Start I> (starting overload function 51),
- Start I>> (starting short-circuit function 50),
- Start IE> (starting ground fault function 51N first threshold),
- Start IE>> (starting ground fault function 50N second threshold),
- Trip I> (overload function 51 trip),
- Trip I>> (short-circuit function 50 trip),
- Trip IE> (ground fault function 51N first threshold trip),
- Trip IE>> (ground fault function 50N second threshold trip),
- Open 52 (breaker open command),
- Close 52 (breaker close command),