94
94
SIF5600 - Manual - 03 - 2008
WREG NUM=2 Baud rate 9600 (0)
Parity No (0)
Stop bit 1 (0)
WREG NUM=3 Enable TX delay 2 ms (2)
Start TX delay 1 ms (1)
WREG NUM=11 Inp value 300 (300)
Inp unit A (0)
WREG NUM=12 IEnp value 100 (100)
IEnp unit A (0)
WREG NUM=13 Reading Direct (1)
WREG NUM=14 K1 0x00000000
K1 mode DeEn-NoLatch (0)
WREG NUM=15 tTR1 200 ms (20)
WREG NUM=16 K2 0x00000000
K2 mode DeEn-NoLatch (0)
WREG NUM=17 tTR2 200 ms (20)
WREG NUM=18 K3 0x00000000
K3 mode DeEn-NoLatch (0)
WREG NUM=19 tTR3 200 ms (20)
WREG NUM=20 K4 0x00000000
K4 mode DeEn-NoLatch (0)
WREG NUM=21 tTR4 200 ms (20)
WREG NUM=22 I curve Independent (0)
WREG NUM=23 I> indep 1.00 In (1000)
WREG NUM=24 t> indep 400 ms (40)
WREG NUM=25 I> dep 1.00 In (1000)
WREG NUM=26 t> dep 1.00 s (100)
WREG NUM=27 I>> indep 7.00 In (7000)
WREG NUM=28 t>> indep 30 ms (3)
WREG NUM=29 IE curve Independent (0)
WREG NUM=30 IE> indep 0.030 In (30)
WREG NUM=31 tE> indep 1.00 s (100)
WREG NUM=32 IE> dep 0.030 In (30)
WREG NUM=33 tE> dep 1.00 s (100)
WREG NUM=34 IE>> indep 0.050 In (50)
WREG NUM=35 tE>> indep 40 ms (4)
WREG NUM=36 Blin I>> Off (0)
WREG NUM=37 Blin IE>> Off (0)
WREG NUM=38 Blout I>> Off (0)
WREG NUM=39 Blout IE>> Off (0)
WREG NUM=40 tF enable On (1)
WREG NUM=41 tF 0.250 s (25)