HX7+ ASD Installation and Operation Manual 91
S1 – S4 Input Terminal Delay
Program Terminal Selection In Terminal Delays
This parameter delays the response of the drive to any change in the S1 – S4
terminal input by the programmed value (see waveforms at
F140).
The delay may be increased to provide additional electrical noise immunity or
to prevent the ASD from responding to contact bounce or chatter.
Direct Access Number — F144
Parameter Type — Numerical
Factory Default 8.0
Changeable During Run — No
Minimum — 2.0
Maximum — 200.0
Units — mS
S5 – S16 Input Terminal Delay
Program Terminal Selection In Terminal Delays
This parameter delays the response of the drive to any change in the S5 – S16
terminal input by the programmed value (see waveforms at
F140).
The delay may be increased to provide additional electrical noise immunity or
to prevent the ASD from responding to contact bounce or chatter.
Direct Access Number — F145
Parameter Type — Numerical
Factory Default 8.0
Changeable During Run — No
Minimum — 2.0
Maximum — 200.0
Units — mS
OUT1 On Delay
Program Terminal Selection Out Terminal Delays
Once the condition is met to close the OUT1 (A & C) output terminals, this
parameter delays the closing of the terminals by the programmed value.
For example, if the OUT1 function is programmed as Over-Torque Alarm,
OUT1 will close 2.0 mS (the default value for OUT1 On Delay) after the over-
torque condition occurs.
The delay may be increased to prevent relay chatter.
Direct Access Number — F150
Parameter Type — Numerical
Factory Default 2.0
Changeable During Run — No
Minimum — 2.0
Maximum — 200.0
Units — mS
OUT2 On Delay
Program Terminal Selection Out Terminal Delays
This parameter delays the closing of the OUT2 (A & C) output terminals by the
programmed value (see waveforms at
F150).
The delay may be increased to prevent relay chatter.
Direct Access Number — F151
Parameter Type — Numerical
Factory Default 2.0
Changeable During Run — No
Minimum — 2.0
Maximum — 200.0
Units — mS
F144 F151