92 HX7+ ASD Installation and Operation Manual
FL On Delay
Program Terminal Selection Out Terminal Delays
This parameter delays the closing of the FL output terminals by the 
programmed value (see waveforms at 
F150).
The delay may be increased to prevent relay chatter.
Direct Access Number —  F152
Parameter Type — Numerical
Factory Default — 2.0
Changeable During Run — No
Minimum — 2.0
Maximum — 200.0
Units — mS
OUT4 On Delay
Program Terminal Selection Out Terminal Delays
This parameter delays the closing of the OUT4 output terminals by the 
programmed value (see waveforms at 
F150).
The delay may be increased to prevent relay chatter.
Direct Access Number —  F153
Parameter Type — Numerical
Factory Default — 2.0
Changeable During Run — No
Minimum — 2.0
Maximum — 200.0
Units — mS
OUT5 On Delay
Program Terminal Selection Out Terminal Delays
This parameter delays the closing of the OUT5 output terminals by the 
programmed value (see waveforms at 
F150).
The delay may be increased to prevent relay chatter.
Direct Access Number —  F154
Parameter Type — Numerical
Factory Default — 2.0
Changeable During Run — No
Minimum — 2.0
Maximum — 200.0
Units — mS
OUT6 On Delay
Program Terminal Selection Out Terminal Delays
This parameter delays the closing of the OUT6 output terminals by the 
programmed value (see waveforms at 
F150).
The delay may be increased to prevent relay chatter.
Direct Access Number —  F155
Parameter Type — Numerical
Factory Default — 2.0
Changeable During Run — No
Minimum — 2.0
Maximum — 200.0
Units — mS
OUT7 On Delay
Program Terminal Selection Out Terminal Delays
This parameter delays the closing of the OUT7 output terminals by the 
programmed value (see waveforms at 
F150).
The delay may be increased to prevent relay chatter.
Direct Access Number —  F156
Parameter Type — Numerical
Factory Default — 2.0
Changeable During Run — No
Minimum — 2.0
Maximum — 200.0
Units — mS
F152 F156