94 HX7+ ASD Installation and Operation Manual
OUT6 Off Delay
Program Terminal Selection Out Terminal Delays
This parameter delays the opening of the OUT6 output terminals by the 
programmed value (see waveforms at 
F160).
The delay may be increased to allow the devices that are connected to OUT6 to 
respond.
Direct Access Number —  F165
Parameter Type — Numerical
Factory Default — 2.0
Changeable During Run — No
Minimum — 2.0
Maximum — 200.0
Units — mS
OUT7 Off Delay
Program Terminal Selection Out Terminal Delays
This parameter delays the opening of the OUT7 output terminals by the 
programmed value (see waveforms at 
F160).
The delay may be increased to allow the devices that are connected to OUT7 to 
respond.
Direct Access Number —  F166
Parameter Type — Numerical
Factory Default — 2.0
Changeable During Run — No
Minimum — 2.0
Maximum — 200.0
Units — mS
Motor #2 Base Frequency
Program Motor Parameters Motor Set #2
The Motor #2 Base Frequency setting is the frequency at which the output 
voltage of the ASD reaches its maximum setting. The #2 Maximum Output 
Voltage is set at 
F171.
This parameter is used only when the parameters for motor set #2 are 
configured and selected. Motor set #2 may be selected by a properly configured 
input terminal.
For proper motor operation, the Base Frequency should be set for the name-
plated frequency of the motor.
Direct Access Number —  F170
Parameter Type — Numerical
Factory Default — 60.0
Changeable During Run — Ye s
Minimum — 25.0
Maximum — 299.0
Units — Hz
Motor #2 Max Output Voltage
Program Motor Parameters Motor Set #2
The Motor #2 Maximum Output Voltage is the Motor #2 output voltage at 
the Base Frequency (
F170). Regardless of the programmed value, the output 
voltage cannot be higher than the input voltage.
The actual output voltage will be influenced by the input voltage of the ASD 
and the Supply Voltage Compensation setting (
F307).
This parameter is used only when the parameters for motor set #2 are 
configured and selected. Motor set #2 may be selected by a properly configured 
input terminal.
Direct Access Number —  F171
Parameter Type — Numerical
Factory Default — (ASD dependent)
Changeable During Run — Ye s
Minimum — 0.0
Maximum — 600.0
Units — Volts
Motor #2 Torque Boost
Program Motor Parameters Motor Set #2
The Motor #2 Torque Boost function is used to increase the low frequency 
torque for high inertia loads by increasing the output voltage at frequencies 
below ½ of the #2 Base Frequency setting (F170).
See parameter F016 (Motor #1 Torque Boost) for an explanation of torque 
boost.
This parameter is used only when the parameters for motor set #2 are 
configured and selected. Motor set #2 may be selected by a properly configured 
input terminal.
Direct Access Number —  F172
Parameter Type — Numerical
Factory Default — (ASD dependent)
Changeable During Run — Ye s
Minimum — 0.0
Maximum — 30.0
Units — %