120 HX7+ ASD Installation and Operation Manual
Motor Shaft Stationary Control
Program Protection DC Braking
This parameter Enables/Disables a continuous DC injection at half of the
amperage setting of
F251 into a stopped motor. This feature is useful in
preheating the motor or to keep the rotor from spinning freely.
Motor Shaft Stationary Control starts after the DC injection brake stops the
motor and continues until STCC is opened, power is turned off, receiving an
Emergency Off command, or this parameter is changed.
Enabling this feature will also require a non-zero entry at F250.
Settings:
0 — Enabled (box checked)
1 — Disabled
Direct Access Number — F254
Parameter Type — Check Box
Factory Default Disabled
Changeable During Run — Ye s
0 Hz Command Function
Program Special Control Special Parameters
This parameter selects the go-to-zero method to be used by the ASD when the
ASD is commanded to go to zero Hz.
Settings:
0 — Standard (DC Injection Braking)
1 — 0 Hz Command
Direct Access Number — F255
Parameter Type — Selection List
Factory Default Standard (DC
Injection Braking)
Changeable During Run — No
F254 F255