HX7+ ASD Installation and Operation Manual 121
Jog Run Frequency
Program Frequency Setting Jog Settings
This parameter sets the output frequency of the drive during a Jog. Jogging is 
the term used to describe turning the motor on for small increments of time and 
is used when precise positioning of motor-driven equipment is required.
Enabling the Jog Window allows for the Manual Jog window to be among the 
screens accessed during repeated MON/PRG entries. This screen must be 
displayed when Jogging using the keypad.
The Jog function may be initiated from the keypad or remotely via the 
Terminal Board or using Communications (for further information on using 
Communications for Jogging, see the Communications manual).
To perform a Jog, set this parameter (F260) to the desired Jog frequency.
Select a Jog Stop method (F261).
Jog Setup Using the Keypad
To initiate a Jog from the keypad perform the following:
1. Place a check in the Enable Jog Window box (Program Frequency 
Setting Jog Settings Enable Jog Window).
Note: The Jog Window must be displayed on the keypad to perform the 
Jog function using the keypad.
2.Press MON/PRG to access the Jog Window.
3.Using the Up/Down arrow keys of the keypad, select Reverse or 
Forward.
4.Place the system in the Local mode (Local|Remote LED is on).
5.Press and hold the Run key for the desired Jog duration.
Jog Setup Using the Terminal Board
To initiate a Jog from the Terminal Board perform the following:
1. Assign a discrete input terminal to the Jog function (see Table 14 on pg. 
189).
2.Assign a discrete input terminal to the F (Forward) function (and 
Reverse if required) (see 
Table 14 on pg. 189).
3.Provide a Forward and/or Reverse command from the Terminal Board.
4.From the Jog Window, use the Up/Down arrow keys of the keypad to 
select Reverse or Forward (Program Frequency Setting Jog 
Settings Enable Jog Window). Press MON/PRG to access the Jog 
Window.
5.Place the system in the Remote mode (Local|Remote LED is off).
6.Connect the assigned Jog terminal (from step 1) to CC for the desired 
Jog duration.
Direct Access Number —  F260
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Ye s
Minimum — 0.00
Maximum — 20.00
Units — Hz
F260 F260