122 HX7+ ASD Installation and Operation Manual
Jog Stop Control
Program Frequency Setting Jog Settings
This parameter sets the stopping method used while operating in the Jog mode.
Settings:
0 — Deceleration Stop
1 — Coast Stop
2 — DC Injection Braking Stop
Direct Access Number —  F261
Parameter Type — Selection List
Factory Default — Deceleration Stop
Changeable During Run — Ye s
Jump Frequency #1
Program Special Control Jump Frequencies
In conjunction with parameter F271, this parameter establishes a user-defined 
frequency range: the Jump Frequency and a plus-or-minus value. During 
acceleration, the output frequency of the drive will hold at the frequency of the 
lower level of the Jump Frequency range until the programmed acceleration 
ramp reaches the upper level of the Jump Frequency range. Then, the output 
frequency of the drive will accelerate to the upper level of the Jump 
Frequency range and continue upward as programmed.
During deceleration, the output frequency of the drive will hold at the 
frequency of the upper level of the Jump Frequency range until the 
programmed deceleration ramp reaches the lower level of the Jump Frequency 
range. Then, the output frequency of the drive will decelerate to the lower level 
of the Jump Frequency range and continue downward as programmed.
Once set up and enabled, it is on in all control modes.
User-selected frequencies may be jumped to avoid the negative effects of 
mechanical resonance.
Direct Access Number —  F270
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Ye s
Minimum — 0.00
Maximum — Max. Freq. (F011)
Units — Hz
Jump Frequency #1 Bandwidth
Program Special Control Jump Frequencies
This parameter establishes a plus-or-minus value for Jump Frequency #1 (see 
F270).
Direct Access Number —  F271
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Ye s
Minimum — 0.00
Maximum — 30.00
Units — Hz
Jump Frequency #2
Program Special Control Jump Frequencies
Same as Jump Frequency #1 (F270) and is used when multiple frequencies are 
to be jumped (see the plus-or-minus value setting at F273). When multiple 
jump frequencies overlap, the system will recognize the lowest and the highest 
frequencies as one jump range.
Direct Access Number —  F272
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Ye s
Minimum — 0.00
Maximum — Max. Freq. (F011)
Units — Hz
Jump Frequency #2 Bandwidth
Program Special Control Jump Frequencies
This parameter establishes a plus-or-minus value for Jump Frequency #2 
(
F272).
Direct Access Number —  F273
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Ye s
Minimum — 0.00
Maximum — 30.0
Units — Hz
F261 F273