HX7+ ASD Installation and Operation Manual 75
Accel #1 Time
Program Fundamentals Accel/Decel #1 Settings
This parameter specifies the time in seconds for the drive to go from 0.0 Hz to 
the Maximum Frequency for the #1 Acceleration profile. The accel/decel 
pattern may be set using F502. The minimum accel/decel time may be set using 
F508.
Note: An acceleration time shorter than the load will allow may cause 
nuisance tripping and mechanical stress to loads.
Automatic Accel/Decel and Stall settings may lengthen the 
acceleration time.
Acceleration
The acceleration rate of a motor is determined by several factors: applied 
power, applied load, and the physical properties of the motor (winding 
parameters, motor size, etc.). The ASD will control the first of these factors: 
input power. The settings of the ASD control the frequency and amplitude of 
the applied voltage to the motor.
Under most operating conditions, as the output frequency of the drive goes up 
so does the output voltage (linear acceleration). The ASD has the ability to 
modify the relationship between frequency and voltage automatically to 
produce smoother operation or increased (starting) torque.
Direct Access Number —  F009
Parameter Type — Numerical
Factory Default — (ASD dependent)
Changeable During Run — Ye s
Minimum — 0.1
Maximum — 6000
Units — Seconds
Decel #1 Time
Program Fundamentals Accel/Decel #1 Settings
This parameter specifies the time in seconds for the drive to go from the 
Maximum Frequency to 0.0 Hz for the #1 Deceleration profile. The accel/
decel pattern may be set using F502.
When operating with the Automatic Accel/Decel enabled (F000) the minimum 
accel/decel time may be set using F508.
Note: A deceleration time shorter than the load will allow may cause 
nuisance tripping and mechanical stress to loads.
Automatic Accel/Decel and Stall settings may lengthen the 
acceleration time.
Direct Access Number —  F010
Parameter Type — Numerical
Factory Default — (ASD dependent)
Changeable During Run — Ye s
Minimum — 0.1
Maximum — 6000
Units — Seconds
Maximum Frequency
Program Fundamentals Frequency Settings
This setting determines the absolute maximum frequency that the ASD can 
output. This setting is also referred to as FH.
Accel/decel times are calculated based on the Maximum Frequency setting.
Note: This setting may not be lower than the Upper Limit setting 
(
F012).
Direct Access Number —  F011
Parameter Type — Numerical
Factory Default — 80.0
Changeable During Run — No
Minimum — 30.0
Maximum — 299.0
Units — Hz
F009 F011