74 HX7+ ASD Installation and Operation Manual
FM Terminal Adjustment
Program Meter Terminal Adjustment
This function is used to calibrate the FM analog output terminal.
To calibrate the FM analog output, connect a meter (current or voltage) as
described at
F005.
With the drive running at a known frequency, adjust this parameter (F006) until
the running frequency produces the desired DC level output at the FM terminal.
Direct Access Number — F006
Parameter Type — Numerical
Factory Default — 512
Changeable During Run — Ye s
Minimum — 0
Maximum — 1280
Type Reset
Program Utility Parameters
This feature assists the user when performing fault analysis or by
allowing a quick system setup change when required. Performing a
Type Reset results in one of the following user-selected post-reset
configurations.
Settings:
0 — None
1 — Auto Setup for 50 Hz
2 — Auto Setup for 60 Hz
3 — Restore Factory Defaults
4 — Clear Trip
5 — Clear Run Timer
6 — New Base Drive Board
7 — *Save User Parameters
8 — Restore User Parameters
9 — Reload EOI Flash (keypad)
10 — Reset EOI Memory (keypad)
Note: *User settings that are stored in the memory of the keypad are
not saved via the Save User Parameters selection. The unsaved
functions include the EOI Option Setups, (Utility Parameters
Display Units, and (Monitor Setup ) Scrolling Monitor.
Direct Access Number — F007
Parameter Type — Selection List
Factory Default — None
Changeable During Run — No
Direction (of motor rotation)
No path available (Direct Access Only)
While operating using the CN8 Option (LED Keypad) this parameter sets the
direction of motor rotation. This setting may be changed during operation. This
setting will not override parameter
F311 (Forward/Reverse Disable).
If either direction is disabled via parameter F311, the disabled direction will not
be recognized if commanded by the
CN8 Option
. If both directions are
disabled via parameter
F311, the direction command from the CN8 Option will
determine the direction of the motor rotation.
Settings:
0 — Forward
1 — Reverse
Note: Press ESC from the
Frequency Command
screen to access the
Motor Direction parameter.
Direct Access Number — F008
Parameter Type — Selection List
Factory Default — Forward
Changeable During Run — Ye s
e Use
ameters
set
F006 F008