HX7+ ASD Installation and Operation Manual 123
Jump Frequency #3
Program Special Control Jump Frequencies
Same as Jump Frequency #1 (F270) and is used when multiple frequencies are
to be jumped (see the plus-or-minus value setting at F275). When multiple
jump frequencies overlap, the system will recognize the lowest and the highest
frequencies as one jump range.
Direct Access Number — F274
Parameter Type — Numerical
Factory Default 0.00
Changeable During Run — Ye s
Minimum — 0.00
Maximum — Max. Freq. (F011)
Units — Hz
Jump Frequency #3 Bandwidth
Program Special Control Jump Frequencies
This parameter establishes a plus-or-minus value for Jump Frequency #3
(
F274).
Direct Access Number — F275
Parameter Type — Numerical
Factory Default 0.00
Changeable During Run — Ye s
Minimum — 0.00
Maximum — 30.0
Units — Hz
Jump Frequency Processing
Program Special Control Jump Frequencies
This parameter determines if the output frequency of the ASD or the PID
feedback signal will be used as a reference for determining the Jump
Frequency range.
See F270 for further information on the Jump Frequency settings.
Settings:
0 — Process Amount (use PID feedback)
1 — Output Frequency
Direct Access Number — F276
Parameter Type — Selection List
Factory Default Process Amount
Changeable During Run — Ye s
Preset Speed #8
Program Pattern Run Preset Speeds
This parameter assigns an output frequency to binary number 1000 and is
identified as Preset Speed #8. The binary number is applied to S1S4 of the
Terminal Board to output the Preset Speed (see
F018 for further information
on this parameter).
Direct Access Number — F287
Parameter Type — Numerical
Factory Default 0.00
Changeable During Run — Ye s
Minimum — Lower Limit (F013)
Maximum — Upper Limit (F012)
Units — Hz
Preset Speed #9
Program Pattern Run Preset Speeds
This parameter assigns an output frequency to binary number 1001 and is
identified as Preset Speed #9. The binary number is applied to S1S4 of the
Terminal Board to output the Preset Speed (see
F018 for further information
on this parameter).
Direct Access Number — F288
Parameter Type — Numerical
Factory Default 0.0
Changeable During Run — Ye s
Minimum — Lower Limit (F013)
Maximum — Upper Limit (F012)
Units — Hz
F274 F288