146 HX7+ ASD Installation and Operation Manual
Torque Command Mode
Program Torque Setting Torque Speed Limit
This parameter specifies whether the torque command function is to be used in 
one direction or both (F/R).
Settings:
0 — Fixed Direction
1 — F/R Permitted
Direct Access Number —  F429
Parameter Type — Selection List
Factory Default — Fixed Direction
Changeable During Run — No
Speed Limit (torque) Reference
Program Torque Setting Torque Speed Limit
The system has the ability to limit the amount that the speed may vary as a 
function of a changing load while operating in the Torque Control mode. This 
parameter sets the input terminal that will be used to control the allowable 
speed variance.
Settings:
0 — None
1 — VI/II
2 — RR
3 — RX
4 — RX2 (option)
5 — Fixed
Direct Access Number —  F430
Parameter Type — Selection List
Factory Default — None
Changeable During Run — Ye s
Speed Limit Torque Level
Program Torque Setting Torque Speed Limit
The system has the ability to limit the amount that the speed may vary as a 
function of a changing load while operating in the Torque Control mode. This 
parameter sets the targeted speed. The plus-or-minus value (range) for this 
setting may be set at 
F432.
Direct Access Number —  F431
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Ye s
Minimum — 0.00
Maximum — Max. Freq. (F011)
Units — Hz
Speed Limit Torque Range
Program Torque Setting Torque Speed Limit
The system has the ability to limit the amount that the speed may vary as a 
function of a changing load while operating in the Torque Control mode. This 
parameter sets a plus-or-minus value (range) for the Speed Limit Torque Level 
(
F431).
Direct Access Number —  F432
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Ye s
Minimum — 0.00
Maximum — Max. Freq. (F011)
Units — Hz
Speed Limit Torque Recovery
Program Torque Setting Torque Speed Limit
The system has the ability to limit the amount that the speed may vary as a 
function of a changing load while operating in the Torque Control mode. This 
parameter sets the response time of the system to torque change requirements.
Direct Access Number —  F433
Parameter Type — Numerical
Factory Default — 0.20
Changeable During Run — No
Minimum — 0.00
Maximum — 2.50
Units — Seconds
F429 F433