HX7+ ASD Installation and Operation Manual 147
Power Running (Driving) Torque Limit #1
Program Torque Setting Torque Limit Settings
This parameter determines the source of the control signal for the positive 
torque limit setting. If Setting is selected, the value set at 
F441 is used as the 
Power Running Torque Limit #1 input.
Settings:
1 — VI/II
2 — RR
3 — RX
4 — RX2 (option)
5 — Setting (of F441)
Direct Access Number —  F440
Parameter Type — Selection List
Factory Default — Setting
Changeable During Run — Ye s
Driving Torque Limit #1 Setting
Program Torque Setting Manual Torque Limit
This parameter provides a value for the Power Running Torque Limit #1 
setting if Setting is selected at 
F440. This value provides the positive torque 
upper limit for the #1 motor.
Direct Access Number —  F441
Parameter Type — Numerical
Factory Default — 250.0
Changeable During Run — Ye s
Minimum — 0.00
Maximum — 250.0
Units — %
Regeneration Torque Limit #1
Program Torque Setting Torque Limit Settings
This parameter determines the source of the Regenerative Torque Limit 
control signal. If Setting is selected, the value set at 
F443 is used for this 
parameter.
Settings:
1 — VI/II
2 — RR
3 — RX
4 — RX2 (option)
5 — Setting (of F443)
Direct Access Number —  F442
Parameter Type — Selection List
Factory Default — Setting
Changeable During Run — Ye s
Regeneration Torque Limit Setting #1
Program Torque Setting Torque Limit Settings Manual Settings
This parameter provides a value to be used as the Regeneration Torque Limit 
#1 if Setting is selected at 
F442.
Direct Access Number —  F443
Parameter Type — Numerical
Factory Default — 250.0
Changeable During Run — Ye s
Minimum — 0.00
Maximum — 250.0
Units — %
Driving Torque Limit #2
Program Torque Setting Manual Torque Limit
This parameter is used to set the positive torque upper limit for the #2 motor 
profile when multiple motors are controlled by a single drive or when a single 
motor is to be controlled by multiple profiles.
Direct Access Number —  F444
Parameter Type — Numerical
Factory Default — 250.0
Changeable During Run — Ye s
Minimum — 0.00
Maximum — 250.0
Units — %
F440 F444