148 HX7+ ASD Installation and Operation Manual
Regeneration Torque Limit #2
Program Torque Setting Manual Torque Limit
This parameter is used to set the negative torque upper limit for the #2 motor 
profile when multiple motors are controlled by a single drive or when a single 
motor is to be controlled by multiple profiles.
Direct Access Number —  F445
Parameter Type — Numerical
Factory Default — 250.0
Changeable During Run — Ye s
Minimum — 0.00
Maximum — 250.0
Units — %
Driving Torque Limit #3
Program Torque Setting Manual Torque Limit
This parameter is used to set the positive torque upper limit for the #3 motor 
profile when multiple motors are controlled by a single drive or when a single 
motor is to be controlled by multiple profiles.
Direct Access Number —  F446
Parameter Type — Numerical
Factory Default — 250.0
Changeable During Run — Ye s
Minimum — 0.00
Maximum — 250.0
Units — %
Regeneration Torque Limit #3
Program Torque Setting Manual Torque Limit
This parameter is used to set the negative torque upper limit for the #3 motor 
profile when multiple motors are controlled by a single drive or when a single 
motor is to be controlled by multiple profiles.
Direct Access Number —  F447
Parameter Type — Numerical
Factory Default — 250.0
Changeable During Run — Ye s
Minimum — 0.00
Maximum — 250.0
Units — %
Driving Torque Limit #4
Program Torque Setting Manual Torque Limit
This parameter is used to set the positive torque upper limit for the #4 motor 
profile when multiple motors are controlled by a single drive or when a single 
motor is to be controlled by multiple profiles.
Direct Access Number —  F448
Parameter Type — Numerical
Factory Default — 250.0
Changeable During Run — Ye s
Minimum — 0.00
Maximum — 250.0
Units — %
Regeneration Torque Limit #4
Program Torque Setting Manual Torque Limit
This parameter is used to set the negative torque upper limit for the #4 motor 
profile when multiple motors are controlled by a single drive or when a single 
motor is to be controlled by multiple profiles.
Direct Access Number —  F449
Parameter Type — Numerical
Factory Default — 250.0
Changeable During Run — Ye s
Minimum — 0.00
Maximum — 250.0
Units — %
Torque Limit Mode
Program Torque Setting Torque Limit Settings
Contact the Toshiba Customer Support Center for information on this 
parameter.
Settings:
0 — Driving/Regen
1 — Positive/Negative
Direct Access Number —  F450
Parameter Type — Selection List
Factory Default — Driving/Regen
Changeable During Run — No
F445 F450